Parameter Measurement of Four-circuit AC Lines on Same Tower
DOI: 469 Downloads 8228 Views
Author(s)
Abstract
The paper presents a method to measure the parameters of four circuits AC lines on the same tower. At first, the positive sequence open circuit impedance and short circuit impedance are both measured for any one of four lines. Secondly, four cases of 2-phase systems are assembled by four lines on the same tower, and then the open circuit impedance and short circuit impedance of 2-phase systems are measured for each case. Based on open circuit impedance and short circuit impedance measurements above, the distributed impedance and admittance for each case are accordingly estimated. Finally, the mutual inductance and coupling capacitance, as well as self-parameters of each line can be calculated.
Keywords
transmission line; parameter measurement of AC line, four circuit AC line on same tower, telegraph equation
Cite this paper
XIAO Yao, DENG Jun, FAN Yi, CHENG Lan,
Parameter Measurement of Four-circuit AC Lines on Same Tower
, SCIREA Journal of Electrical Engineering.
Volume 1, Issue 1, October 2016 | PP. 1-14.
References
[ 1 ] | HU Zhijian,XIONG Min, LI Yan, et al, Measurement method of zero sequence param-eters of EHV four-circuit transmission lines on the same tower, Proceedings of the CSEE[J], 2015, 35(17): 4548-4556. |
[ 2 ] | Morched A, Gustavsen B, Tartibi M. A universal model for accurate calculation of electromagnetic transients on overhead lines and underground cables [J]. IEEE Transactions on Power Delivery, 1999, 14(3): 1032-1038. |
[ 3 ] | LI Shusen, CHEN Xiaoyan, QI Geqing et al. Et al. Discussion on Live Line Measurement of the Parameters of the Transmission Lines with Four-circuit on a Tower [J]. High Voltage Engineering, 2006, 32(7):17-20. |
[ 4 ] | HU Zhijian, CHEN Yunping, HU Nin. New live line measurement methods of trans-mission lines’ inductance parameters based on GPS[C]//2004 International Conference on Power System Technology.Singapore: IEEE, 2004: 63-68. |
[ 5 ] | XIAO Yao, DENG Jun, FAN Yi, et al, De-coupling Measurement of Zero Sequence Pa-rameters for Four-circuit AC Transmission Lines on Same Tower[J], Southern Power System Technology, 2016, 10(1): 54-59 |